  1. ONLY AUTHORIZED  MAINTENANCE PERSONNEL SHOULD ENTER ADVANCED MENU AND MAKE CHANGES Picture 1. Press Menu Button Picture 2. Press Advanced to enter Advanced menu
    • ONLY AUTHORIZED MAINTENANCE PERSONNEL SHOULD ENTER ADVANCED MENU AND MAKE CHANGES

    • Picture 1. Press Menu Button

    • Picture 2. Press Advanced to enter Advanced menu

    • Picture 3. Enter Admin Password Menu appears

    • Use the numbers to enter 4 digit factory preset password. Number is being displayed in the blue ribbon

    • Press DEL button to delete incorrect number

    • Press OK to confirm input

  2. Picture 1. Press AI Min Max button to enter AI Min Max menu Picture 2. You entered AI Min Max menu
    • Picture 1. Press AI Min Max button to enter AI Min Max menu

    • Picture 2. You entered AI Min Max menu

    • Picture 2. Use Home button to return to Home Screen

    • Picture 2. Use Up button to return to Advanced Menu New line.

    • Picture 2. Use Next and Prev button to navigate through various settings

  3. Analog Input Min Max screen serves to transform voltage level in the range of 0-10V read from Analog Input AI1 or AI2 into a real value in the sensor unit (Temperature - Celsius, Pressure - Pascal, Air Quality - CO2 ppm, Humidity %rH) This transformation depends on the sensor specification, and  can be adjusted here. The value on the Analog Input ranging from 0 - 10.0 V is transformed linearly to a value from Min to Max depending on which sensor is the Fan controlled  (set in Parameters 01 screen)
    • Analog Input Min Max screen serves to transform voltage level in the range of 0-10V read from Analog Input AI1 or AI2 into a real value in the sensor unit (Temperature - Celsius, Pressure - Pascal, Air Quality - CO2 ppm, Humidity %rH) This transformation depends on the sensor specification, and can be adjusted here.

    • The value on the Analog Input ranging from 0 - 10.0 V is transformed linearly to a value from Min to Max depending on which sensor is the Fan controlled (set in Parameters 01 screen)

    • Analog Input 1 is used exclusively for Fan 1 and Analog Input 2 is used exclusively for Fan 2

    • Use + and - buttons to increase or decrease values

    • Press value button to enter Keyboard to input new value

    • Press Save to confirm changes

  4. Go to AinMinMax 3 and 4. This Menu is sets the same range of voltage to sensor value transformation for Analog Input 2 Use + and - buttons to increase or decrease values
    • Go to AinMinMax 3 and 4. This Menu is sets the same range of voltage to sensor value transformation for Analog Input 2

    • Use + and - buttons to increase or decrease values

    • Press value button to enter Keyboard to input new value

    • Press Save to confirm changes