Introduction
Learn how to setup various HVAC application, and configurations, connection etc.
-
-
Home - Menu - Advanced - Parametar
-
Reading value from pressure sensor in range from 0-10VDC on analog input 1.
-
Analog output (AO1) for control fan1 speed 0-10VDC (duct air pressure).
-
BIN - Binary input for alarm or filter indication.
-
UI - Universal input for alarm or filter indication.
-
Analog output (AO2) for control fan2 speed 0-10VDC (duct air pressure).
-
More information about parametars and process which we can regulate you can find : Parametars Configuration
-
-
-
Connection Codis CP with FAN1. Analog output 1 is 0-10VDC.
-
Analog input 1 (0-10VDC). It used only to control Fan 1. Different sensor can be connected to the analog input : Pressure, Temperature,Humidity, Air Quality.
-
Binary input function: binary input can be used to notify several different external events: Fan alarm, Filter status, Run status. More information you can find in IN/OUT description.
-
UI - Universal input can be used to notify several diffrent external events: Fan alarm, Filter and Run status. Also we can use this input to connect remote temperature sensor PT1000. **Home-Menu-Advanced-Parametars - Fan Controlled by = Temp-Fan 1 sensor type = RTD input.
-
Connection Codis CP with FAN2. Analog output 2 is 0-10VDC.
-
Analog input 2 (0-10VDC). It used to control fan 2. Different sensor can be connected to the analog input : Pressure, Temperature,Humidity, Air Quality.
-
BACnet MS/TP network.
-
-
-
Power supply 24 V AC (G;G0).
-
Bacnet MS/TP network (D+;D-;SC).
-
Analog input 1 (AI1;M).
-
RTD input (RTD;RTD).
-
Binary input (BIN;BIN).
-
Analog output 1(AO1;M).
-
Analog output 2 (AO2;M).
-
Analog input 2 (AI2;M).
-
-
-
Setpoint Adjustment Home Screen. Clicking + and - buttons in the left columns changes the Pressure Setpoint + or - 0.5 Pa.
-
Setpoint button with an indication of current setpoint value.
-
Measured pressure value
-
Fan speed button, with an indication of the current fan speed.
-
-
-
Manual start Fan 1. Speed is define in speed button.
-
Manual stop Fan 1.
-
Start and stop is define by time schedule. More about time schedule you can find :Time Schedule
-
Fan speed button.
-
Picture 2. Shows the Manual fan speed Adjustment Home Screen. Clicking + and - buttons in the left columns changes the fan speed + or - 5%.
-
Fan operates in automatic mode according to the PID control.
-
-
-
Setpoint control button.
-
Fan Alarm is used to to notify the C35-FAN device if the external fan suffered important error and stops working. Possible states are Off (normal) and On (not normal - find the cause of error). If the alarm turns on, in the C35-FAN device the Home Screen switches to Alarm screen with appropriate error message and blinking red light
-
Reading value from Analog input.
-
Fan speed button.
-
-
-
Home - Menu - Advanced - Parametar
-
Analog output (AO1) for control fan1 speed 0-10VDC (duct air temperature).
-
Reading value from temperature sensor in range from 0-10VDC on analog input 1.
-
BIN - Binary input for alarm or filter indication.
-
-
-
Analog input 1 (0-10VDC). It used only to control Fan 1.
-
UI - Universal input can be used to notify several diffrent external events: Fan alarm, Filter and Run status. Also we can use this input to connect remote temperature sensor PT1000. **Home-Menu-Advanced-Parametars - Fan Controlled by = Temp-Fan 1 sensor type = RTD input.
-
Connection Codis CP with FAN1. Analog output 1 is 0-10VDC.
-
Connection Codis CP with FAN2. Analog output 2 is 0-10VDC.
-
Binary input function: binary input can be used to notify several different external events: Fan alarm, Filter status, Run status. More information you can find in IN/OUT description.
-
-
-
Setpoint control button.
-
Reading temperature.
-
Fan speed button.
-
Setpoint Adjustment Home Screen. Clicking + and - buttons in the left columns changes the temperature Setpoint + or - 0.5 °C.
-
-
-
Home - Menu - Advanced - Parametar
-
Analog output (AO1) for control fan1 speed 0-10VDC (Air Quality).
-
Reading value from air quality sensor (CO2) in range from 0-10VDC on analog input.
-
Alarm indication on Binary input 1
-
-
-
Analog input 1 (0-10VDC). It used only to control Fan 1.
-
UI - Universal input can be used to notify several diffrent external events: Fan alarm, Filter and Run status. Also we can use this input to connect remote temperature sensor PT1000. **Home-Menu-Advanced-Parametars - Fan Controlled by = Temp-Fan 1 sensor type = RTD input.
-
Connection Codis CP with FAN1. Analog output 1 is 0-10VDC.
-
Connection Codis CP with FAN2. Analog output 2 is 0-10VDC.
-
Analog input 2 (0-10VDC). It used only to control Fan 2.
-
Binary input function: binary input can be used to notify several different external events: Fan alarm, Filter status, Run status. More information you can find in IN/OUT description
-
-
-
Setpoint control button.
-
Reading air quality (Co2).
-
Fan speed button.
-
Setpoint Adjustment Home Screen. Clicking + and - buttons in the left columns changes the air quality Setpoint + or - 50 ppm.
-
-
-
Home - Menu - Advanced - Parametar
-
Analog output (AO1) for control fan1 speed 0-10VDC (Air Humidity).
-
Reading value from air humidity sensor (rH) in range from 0-10VDC on analog input.
-
Alarm indication on Binary input
-
-
-
Analog input 1 (0-10VDC). It used only to control Fan 1.
-
UI - Universal input can be used to notify several diffrent external events: Fan alarm, Filter and Run status. Also we can use this input to connect remote temperature sensor PT1000. **Home-Menu-Advanced-Parametars - Fan Controlled by = Temp-Fan 1 sensor type = RTD input.
-
Connection Codis CP with FAN1. Analog output 1 is 0-10VDC.
-
Connection Codis CP with FAN2. Analog output 2 is 0-10VDC.
-
Analog input 2 (0-10VDC). It used only to control Fan 2.
-
Binary input function: binary input can be used to notify several different external events: Fan alarm, Filter status, Run status. More information you can find in IN/OUT
-
-
-
Setpoint control button.
-
Reading air humidity (rH).
-
Fan speed button.
-
Setpoint Adjustment Home Screen. Clicking + and - buttons in the left columns changes the air quality Setpoint + or - 1 % rH.
-