Introduction
Learn how to setup various fan parameters and configurations, EC motor voltages, etc.
Unpublished & Confidential
Only for internal use and for testing purposises
-
-
Picture 1. Press Menu Button
-
Picture 2. Press Advanced to enter Advanced menu
-
Picture 3. Enter Admin Password Menu appears
-
Use the numbers to enter 4 digit factory preset password. Number is being displayed in the blue ribbon
-
Press DEL button to delete incorrect number
-
Press OK to confirm input
-
-
-
Picture 1. Press Parameter button to enter Parameter menu
-
Picture 2. You entered Parameter menu
-
Picture 2. Use Home button to return to Home Screen
-
Picture 2. Use Up button to return to Advanced Menu New line.
-
Picture 2. Use Next and Prev button to navigate through various settings
-
-
-
Go to Parameters 1 / 7 Menu. There are separate options of each fan, Fan 1 and Fan 2. You can configure each fan to be different type
-
Fan 1 motor type:The Fan motor type defines whether the controlled fan coil is equipped with EC motor fan, or a 3 or 1 speed motor fan. This setting will affect analog output AO1 voltages
-
Fan motor type: EC motor- By selecting EC motor, user will be able to select any fan speed with 5% interval plus AUTO fan working mode and OFF mode
-
Fan motor type: 3 speed motor - By selecting 3 speed motor user will be able to select one or three fan speeds, AUTO fan working mode and OFF mode
-
Fan 2 motor type:The Fan motor type defines whether the controlled fan coil is equipped with EC motor fan, or a 3 or 1 speed motor fan. This setting will affect analog output AO2 voltages
-
Fan motor type: EC motor- By selecting EC motor, user will be able to select any fan speed with 5% interval plus AUTO fan working mode and OFF mode
-
Fan motor type: 3 speed motor - By selecting 3 speed motor user will be able to select one or three fan speeds, AUTO fan working mode and OFF mode
-
Press Save to confirm changes
-
-
-
Go to Parameters 1 / 7 Menu. There are separate options of each fan, Fan 1 and Fan 2. You can configure each fan to be different type
-
Fan controlled by - determines the type of proccess we want to regulate. Can be: Pressure, Temperature, Air Quality (CO2) and Humidity
-
Fan sensor type - determines which type of sensor should be used: internal Codis sensors, or external sensors connected to Analog inputs, or RTD input. Can be: Internal, Analog Input AI1/AI2 and RTD input if fan is controlled by Temperature
-
Example: this set up is if the Fan 1 is EC motor set to keep the setpoint of Pressure level in the pipe sensor connected to analog input, and the Fan 2 is set to control a 3 speed motor to keep the temperature setpoint on the RTD sensor
-
-
-
Go to Parameters 2/7 menu. This Menu is for setting the voltage levels for FAN 1, whether it is 3 speed or EC motor type
-
Fan 1 speed Voltages: sets the voltage levels on Analog Outputs for each possible speed. Available speeds are:
-
OFF Voltage: If this value is different from zero volts for the controlled 3 speed motor fan, adjust the Fan speed OFF voltage to a value that will turn off the 3 speed fan.
-
Speed Voltage: Defines the signal value and voltage level for the each speed of the fan. Adjust according to Fan specification
-
Use + and - buttons to increase or decrease values
-
Press value button to enter Keyboard to input voltage number. Voltage values are in range from 0V - 10.0 V
-
Press Save to confirm changes
-
-
-
ECM voltage: The analog output signal (AO1) for the EC motor can be configured with three parameters:
-
ECM OFF Voltage: If this value is different from zero volts for the controlled EC motor fan, adjust the ECM OFF voltage to a value that will turn off the ECM fan.
-
ECM Min Speed Voltage: Defines the minimum signal value and the minimum speed of the fan (20 %)
-
ECM Max Speed Voltage: Defines the maximum signal value and the maximum speed of the fan (100 %)
-
Use + and - buttons to increase or decrease values
-
Press value button to enter Keyboard to input ECM value number. ECM values are in range from 0V - 10.0 V
-
Press Save to confirm changes
-
-
-
Go to Parameters 3/7 menu. This Menu is for setting the voltage levels for FAN 2, whether it is 3 speed or EC motor type
-
-
-
Parameters menus 04, 05, 06, 07 set the PID values to control Fan 1 and Fan 2.
-
Picture 1. Parameters 04 sets the Temperature and Pressure PID values for Fan 1
-
Picture 2. Parameters 05 sets the Air Quality (CO2 level) and Humidity PID values for Fan 1
-
Use + and - buttons to increase or decrease values
-
Press value button to enter Keyboard to input number
-
Press Save to confirm changes
-
-
-
Parameters menus 04, 05, 06, 07 set the PID values to control Fan 1 and Fan 2.
-
Picture 1. Parameters 06 sets the Temperature and Pressure PID values for Fan 2
-
Picture 2. Parameters 07 sets the Air Quality (CO2 level) and Humidity PID values for Fan 2
-
Use + and - buttons to increase or decrease values
-
Press value button to enter Keyboard to input number
-
Press Save to confirm changes
-