  1. ONLY AUTHORIZED  MAINTENANCE PERSONNEL SHOULD ENTER ADVANCED MENU AND MAKE CHANGES Picture 1. Press Menu Button Picture 2. Press Advanced to enter Advanced menu
    • ONLY AUTHORIZED MAINTENANCE PERSONNEL SHOULD ENTER ADVANCED MENU AND MAKE CHANGES

    • Picture 1. Press Menu Button

    • Picture 2. Press Advanced to enter Advanced menu

    • Picture 3. Enter Admin Password Menu appears

    • Use the numbers to enter 4 digit factory preset password . Number is being displayed in the blue ribbon

    • Press DEL button to delete incorrect number

    • Press OK to confirm input

  2. Picture 1. Press HVAC button to enter HVAC menu Picture 2. You entered HVAC Menu
    • Picture 1. Press HVAC button to enter HVAC menu

    • Picture 2. You entered HVAC Menu

    • Picture 2. Use Home button to return to Home Screen

    • Picture 2. Use Up button to return to Advanced Menu

    • Picture 2. Use Next and Prev button to navigate through various settings

  3. Position yourself in HVAC 1/4 menu
    • Position yourself in HVAC 1/4 menu

    • Fan Coil Type setting is used to define system type for the fan (depends on isntallation):

    • 2-pipe cooling: fan can only cool the area

    • 2-pipe heating: fan can only cool the area

    • 2-pipe heat or cool: fan can cool or heat the area depending on changeover options

    • 4-pipe: fan heats or cools depending if the setpoint is higher or lower then the current temperature

  4. Position yourself in HVAC 1/4 menu
    • Position yourself in HVAC 1/4 menu

    • Valve actuator: determines the signal type to control the actuator. Depends on installed equipment. Can be:

    • On/Off : simple binary signal

    • PWM: pulse width modulation signal

    • 0-10V: Voltage between 0 and 10V proportional to percentage of open signal

    • Not available in 4-pipe mode

    • Fan motor type: can be 3 speed or EC motor

  5. Position yourself in HVAC 1/4 menu
    • Position yourself in HVAC 1/4 menu

    • ECM voltage: The analog output signal (AO1) for the EC motor can be configured with three parameters:

    • ECM OFF Voltage: If this value is different from zero volts for the controlled EC motor fan, adjust the ECM OFF voltage to a value that will turn off the ECM fan

    • ECM Min Speed Voltage: Defines the minimum signal value and the minimum speed of the fan (20 %)

    • ECM Max Speed Voltage: Defines the maximum signal value and the maximum speed of the fan (100 %)

    • Use + and - buttons to increase or decrease values

    • Press value button to enter Keyboard to input ECM value number. ECM values are in range from 0V - 10.0 V

    • Press Save to confirm changes

  6. Poisiton yourself in HVAC 2/4 menu
    • Poisiton yourself in HVAC 2/4 menu

    • VAV controlled by: determine which setpoints shall influence turning on VAV output. Can be:

    • Disabled

    • Heating

    • Cooling

    • CO2

    • Heat & CO2

    • Cool & CO2

  7. Position yourself in HVAC 2/4 menu
    • Position yourself in HVAC 2/4 menu

    • Changeover signal: for 2-pipe heat or cool choose the way system selects it works in heating or cooling mode. It can be: Internal or CBMS

    • Heating changeover Temp ???

  8. Adjust settings for PI controller for FAN Temp, VAV Temp and VAV Air Quality
    • Adjust settings for PI controller for FAN Temp, VAV Temp and VAV Air Quality

    • Adjust P-band and I-time for each PI controller

    • P-band determines the speed of change. Higher number = faster change, but more volatile ???

    • I-time determines the slowness of change. Higher number = slower change, but more accurate with less overshoot ??

    • Use + and - buttons to increase values by 0.1

    • Press value button to enter Keyboard to input number

    • Press Save to confirm changes

  9. Position yourself in HVAC 4/4 menu
    • Position yourself in HVAC 4/4 menu

    • Adjust P-band and I-time for each PI controller

    • P-band determines the speed of change. Higher number = faster change, but more volatile

    • I-time determines the slowness of change. Higher number = slower change, but more accurate with less overshoot

    • Use + and - buttons to increase values by 0.1

    • Press value button to enter Keyboard to input number

    • Press Wall type button and select the type of wall Codis is mounted on to fine tune temperature measurement

    • Press Save to confirm changes