Picture 1. Press Menu Button
-
Picture 2. Press Advanced to enter Advanced menu
-
Picture 3. Enter Admin Password Menu appears
-
Use the numbers to enter 4 digit factory preset password . Number is being displayed in the blue ribbon
-
Press DEL button to delete incorrect number
-
Press OK to confirm input
-
-
-
Picture 1. Press HVAC button to enter HVAC menu
-
Picture 2. You entered HVAC Menu
-
Picture 2. Use Home button to return to Home Screen
-
Picture 2. Use Up button to return to Advanced Menu
-
Picture 2. Use Next and Prev button to navigate through various settings
-
-
-
Position yourself in HVAC 1/4 menu
-
Fan Coil Type setting is used to define system type for the fan (depends on isntallation):
-
2-pipe cooling: fan can only cool the area
-
2-pipe heating: fan can only cool the area
-
2-pipe heat or cool: fan can cool or heat the area depending on changeover options
-
4-pipe: fan heats or cools depending if the setpoint is higher or lower then the current temperature
-
-
-
Position yourself in HVAC 1/4 menu
-
Valve actuator: determines the signal type to control the actuator. Depends on installed equipment. Can be:
-
On/Off : simple binary signal
-
PWM: pulse width modulation signal
-
0-10V: Voltage between 0 and 10V proportional to percentage of open signal
-
Fan motor type: can be 3 speed or EC motor
-
-
-
Position yourself in HVAC 1/4 menu
-
ECM voltage: The analog output signal (AO1) for the EC motor can be configured with three parameters:
-
ECM OFF Voltage: If this value is different from zero volts for the controlled EC motor fan, adjust the ECM OFF voltage to a value that will turn off the ECM fan
-
ECM Min Speed Voltage: Defines the minimum signal value and the minimum speed of the fan (20 %)
-
ECM Max Speed Voltage: Defines the maximum signal value and the maximum speed of the fan (100 %)
-
Use + and - buttons to increase or decrease values
-
Press value button to enter Keyboard to input ECM value number. ECM values are in range from 0V - 10.0 V
-
Press Save to confirm changes
-
-
-
Poisiton yourself in HVAC 2/4 menu
-
VAV controlled by: determine which setpoints shall influence turning on VAV output. Can be:
-
Disabled
-
Heating
-
Cooling
-
CO2
-
Heat & CO2
-
Cool & CO2
-
-
-
Position yourself in HVAC 2/4 menu
-
Changeover signal: for 2-pipe heat or cool choose the way system selects it works in heating or cooling mode. It can be: Internal or CBMS
-
Heating changeover Temp ???
-
-
-
Adjust settings for PI controller for FAN Temp, VAV Temp and VAV Air Quality
-
Adjust P-band and I-time for each PI controller
-
P-band determines the speed of change. Higher number = faster change, but more volatile ???
-
I-time determines the slowness of change. Higher number = slower change, but more accurate with less overshoot ??
-
Use + and - buttons to increase values by 0.1
-
Press value button to enter Keyboard to input number
-
Press Save to confirm changes
-
-
-
Position yourself in HVAC 4/4 menu
-
Adjust P-band and I-time for each PI controller
-
P-band determines the speed of change. Higher number = faster change, but more volatile
-
I-time determines the slowness of change. Higher number = slower change, but more accurate with less overshoot
-
Use + and - buttons to increase values by 0.1
-
Press value button to enter Keyboard to input number
-
Press Wall type button and select the type of wall Codis is mounted on to fine tune temperature measurement
-
Press Save to confirm changes
-
Almost done!
Finish Line