Learn how to set and edit various input and output signal configurations, or just view the current values

  1. ONLY AUTHORIZED  MAINTENANCE PERSONNEL SHOULD ENTER ADVANCED MENU AND MAKE CHANGES Picture 1. Press Menu Button Picture 2. Press Advanced to enter Advanced menu
    • ONLY AUTHORIZED MAINTENANCE PERSONNEL SHOULD ENTER ADVANCED MENU AND MAKE CHANGES

    • Picture 1. Press Menu Button

    • Picture 2. Press Advanced to enter Advanced menu

    • Picture 3. Enter Admin Password Menu appears

    • Use the numbers to enter 4 digit factory preset password. Number is being displayed in the blue ribbon

    • Press DEL button to delete incorrect number

    • Press OK to confirm input

  2. Picture 1. Press In Out button to enter In Out menu
    • Picture 1. Press In Out button to enter In Out menu

  3. RTD Sensor function:  has the following options:
    • RTD Sensor function: has the following options:

    • Disabled – default value

    • Changeover sensor

    • If 'Changeover sensor,, the device will automatically change from heating to cooling or vice versa as required. Changeover will be determined by the temperature reading value from RTD sensor. If the temperature is above 28°C, the control mode will change to heating. If the temperature is below 18°C, the control mode will be changed to cooling

    • RTD temperature: If the Analog RTD sensor (PT1000) is connected to the device’s RTD input, current sensor reading value will be displayed, converted to Celsius degrees

    • Press Save to keep changes