Skip to main content

Introduction

Learn how to set and change network settings, BACnet name and address, buad rate of RS485 network

  1. Picture 1. Press Menu Button Picture 2. Press Advanced to enter Advanced menu Pciture 3. Enter Admin Password Menu appears
    • Picture 1. Press Menu Button

    • Picture 2. Press Advanced to enter Advanced menu

    • Pciture 3. Enter Admin Password Menu appears

    • Use the numbers to enter 4 digit factory preset password. Number is being displayed in the blue ribbon

    • Press DEL button to delete incorrect number

    • Press OK to confirm input

  2. Picture 1. Press Network button to enter network Menu Picture 2. Shows Network screen
    • Picture 1. Press Network button to enter network Menu

    • Picture 2. Shows Network screen

    • Picture 2. Use Home button to return to Home Screen

    • Picture 2. Use Up button to return to Advanced Menu

  3. Device name - sets BACnet Name of this device to be shown on RS485 BACnet Network
    • Device name - sets BACnet Name of this device to be shown on RS485 BACnet Network

    • Device ID - BACnet ID of the device to be shown and used on RS485 BACnet Network. Range: 0 - 4194303

    • MS/TP MAC - physical address of the Device on the network. Range: 0 - 127

    • Recommended (but not required) is to have the same value for Device ID and MS/TP MAC address

    • Max master - maximum number of devices on the RS485 BACnet network. Range: 0-127

    • Max info frames - maximum number of data frames to be sent in single BACnet communication. Range: 1-100

    • Baud rate - Setting of the RS485 network. Can be one of the following values: 9600, 15200, 38400, 76800

  4. Picture 1. Press Device name text to edit the Device Name (as will be seen on Network) Picture 2. and Picture 3. Use keyboard to enter name Use DEL button as Backspace delete
    • Picture 1. Press Device name text to edit the Device Name (as will be seen on Network)

    • Picture 2. and Picture 3. Use keyboard to enter name

    • Use DEL button as Backspace delete

    • Use Shift button to put uppercase letters

    • Picture 2. Press 12# button to enter keyboard for numbers and special signs

    • Picture 3. Press ABC button to return to letter keyboard

    • Use Save button to confirm selection

  5. Click various Buttons on the right hand side to edit desired values + button increases the value by 1
    • Click various Buttons on the right hand side to edit desired values

    • + button increases the value by 1

    • - button decreases the value by 1

    • pressing the value button opens the screen to edit the button: Picture 2.

    • Pciture 2. Use keyboard to enter new value. Press OK to confirm or Up button to cancel

    • Above applies to all rows, except baud rate

    • Baud rate buttons cyclically change between preset values of 9600, 15200, 38400, 76800

    • Press Save to confirm changes