Introduction

Winter/Summer season functionality

Main purpose of Winter/Summer season functionality is to control night cooling and relative humidity in winter or summer season.

Season changeover can be done:

  • manually
  • by date
  • automatically with temperature sensor (PT1000)

Night Cooling for Summer season:

If controlled System type is Ventilation & Heating (HVAC menu) with duct heat exchanger for air temperature control in Summer device will not activate heating if supply air temperature is below set point.

Relative humidity control depending on season:

If C35HV device has relative humidity sensor it will activate air flow when relative humidity is higher then set point. Depending on geographic location this option can be useful only in Summer or Winter so it can be enabled or disabled for specific season in HVAC menu

Video Overview

How to change winter/summer season

  1. Picture 1. Press Menu Button
    • Picture 1. Press Menu Button

  2. Press Winter (Picture 1. ) or Summer (Picture 2.) button to enter Season Menu If in In/Out menu setting  RTD input function is W/S Changeover, then Winter/Summer button is locked due to automatic season changeover (picture 3.) If in In/Out menu setting  RTD input function is W/S Changeover, then Winter/Summer button is locked due to automatic season changeover (picture 3.)
    • Press Winter (Picture 1. ) or Summer (Picture 2.) button to enter Season Menu

    • If in In/Out menu setting RTD input function is W/S Changeover, then Winter/Summer button is locked due to automatic season changeover (picture 3.)

  3. Press Season button to change between Summer and Winter  season Change season by date setting has to be Disabled in order to switch season manually
    • Press Season button to change between Summer and Winter season

    • Change season by date setting has to be Disabled in order to switch season manually

    • Button icon on the Menu screen matches the selected Season (e.g. if Summer was selected it will show Summer as Picture 2.)

  4. In In/Out menu RTD input function setting must be different then W/S Changeover to enable season changeover by date
    • In In/Out menu RTD input function setting must be different then W/S Changeover to enable season changeover by date

    • Press Change season by date button to show Enabled

    • Season button has changed to By date and can not be clicked

    • Set Summer start day and Winter start day

  5. Change Summer or Winter season automatically by detecting temperature in the air duct or water pipes with temperature sensor (PT1000) connected to RTD input
    • Change Summer or Winter season automatically by detecting temperature in the air duct or water pipes with temperature sensor (PT1000) connected to RTD input

    • To set automatic season changeover go to Inputs/Outputs in Advanced menu